Home
Product Directory
Instruments & Meters
Meter for Electricity
Other Meters for Electricity
High Voltage Cable Resonance Voltage Withstand Test System
US$5,300.00 - 74,600.00 | 1 Set (MOQ) |
Port:
Ningbo, China
Production Capacity:
2000 Pieces/Year
Payment Terms:
D/P
Hangzhou High Voltage Technology Co., Ltd.
Zhejiang, China
Last Login Date:
Aug 04, 2021
Business Type:
Manufacturer/Factory
Main Products:
Switch Tester, Transformer Tester, Generator Tester, Lightning Arrester Tester, Insulator Tester, Grounding Device Tester, Power Cable Tester, Power Line Tester, AC / DC High Voltage Generator
Find Similar Products
Product Description
Company Info
Basic Info.
Model NO.
CTSR
Trademark
HZHV
Origin
Hangzhou, China
Product Description
It is suitable for ac withstand voltage test of electrical equipment of various voltage levels and AC withstand voltage test of rubber and plastic cables of 220kV and below. For example, alternator, transformer, GIS, switch, busbar, busbar, busbar, busbar, busbar and mutual inductor. The device is composed of frequency conversion control power supply, excitation transformer, reactor, capacitive voltage divider and compensation capacitor.
Functional features:
Portable, dry, oil structure, arbitrary combination, comprehensive functions, a multi-purpose machine
Manual and automatic test mode, automatic tuning, automatic voltage stabilizing, parameter setting
Digital and analog dual monitoring, software and hardware dual overvoltage protection data saving, computer online.
System components:
Technical indicators:
(For non-standard customization, please provide sample type, capacity, voltage class, section, length and other parameters)
Hangzhou High Voltage Technology Co., Ltd. Is a technological enterprise that independently develops, produces and sells high-voltage test equipment! Mainly produce high voltage switches, circuits, transformer direct resistance, on-load tapping, transformer loss parameters, winding deformation, transformers, arresters, generators, partial discharges, dielectric loss tests, frequency resonance withstand voltage tests, earth grid grounding parameters and shunts Vector, secondary and relay protection testing and other high-voltage electrical test equipment.
Obtained 16 international patents and more than 20 software copyright certifications. Self-built 4000 square meters electrical test building, established high-voltage test center and power engineering service team, long-term service for various voltage level test projects and special test projects, relying on the high-voltage test center, at the same time, a high-voltage test undertaking practical operation training class is opened for electric power Industry practitioners provide professional theoretical guidance and practical teaching.
common problem
1. About us
Hangzhou High Voltage Technology Co., Ltd.is a scientific and technological company integrating R&D, production and sales. It independently develops and produces a series of high-voltage test equipment. It was established in 2002 and has a huge production system and business team!
2. Goods inventory and order transportation issues!
After the order is formally formed, the goods will be dispatched within 10 days under normal circumstances. If the purchase volume is large or the customized products are determined according to the actual situation, the goods will be tracked and fed back to the users from time to time during the cargo transportation!
3. Is quality assurance guaranteed?
Twenty years of R&D and production experience, all products have been inspected by the national measurement station, and the quality is guaranteed
4. After-sales service
We promise that all products will provide free two-year warranty, lifetime maintenance, free service information, and online technical services through email, video, etc.
5. Cooperative countries
The products have been successfully exported to the United States, Europe, India, Japan, Australia, Russia and other countries, and distributors have been established in various countries to provide thoughtful services.
contact us:
Hangzhou High Voltage Technology Co., Ltd.
Address: No. 2-15#, Yongtai Road, Renhe Street, Yuhang District, Hangzhou
Contact: Mr. Wang
Functional features:
Portable, dry, oil structure, arbitrary combination, comprehensive functions, a multi-purpose machine
Manual and automatic test mode, automatic tuning, automatic voltage stabilizing, parameter setting
Digital and analog dual monitoring, software and hardware dual overvoltage protection data saving, computer online.
System components:
Device name | Model | Quantity | |
1 | DRIVER TRANSFORMER | JLB- | 1 |
2 | AC POWER SOURCE | CTSR- | 1 |
3 | Reactor | DK- | 3 |
4 | CVD | FCR- | 1 |
5 | ATTCHMENTS | 1 |
Technical indicators:
(For non-standard customization, please provide sample type, capacity, voltage class, section, length and other parameters)
Model NO (CTSR) | Parameter | Test object | |||||||||
Test transformer (kVA/kV) | Power supply(kW) | Reactor (kVA/kV/H) | Capacitive divider(kV/pF) | Voltage classes(kV) | Cross-section of cable(mm2) | Length(km) | Hz | Test Voltage (kV) | |||
44/22 | 3kVA/1.5kV/ 0.4kV | 5.5kW/220/380V | Single node: 22kVA/22kV/110H A total of two | 30kV/3000pF | 10kV | 630mm2 | 0.6km | 30~300Hz | ≤22kV | ||
300mm2 | 1.0km | ||||||||||
120mm2 | 1.2 km | ||||||||||
25mm2 | 2.0km | ||||||||||
88/22 | 6kVA/1.5kV/3kV/0.4kV | 5.5kW/220/380V | Single node: 44kVA/22kV/55H A total of two | 50kV/2500pF | 10kV | 630mm2 | 1.5km | 30~300Hz | ≤22kV | ||
300mm2 | 2.0km | ||||||||||
120mm2 | 2.5km | ||||||||||
25mm2 | 4.5km | ||||||||||
10kV Electrical Equipment | 30~300Hz | ≤42kV | |||||||||
132/22 | 6kVA/1kV/0.4kV | 5.5kW/220/380V | Single node: 44kVA/22kV/55H A total of three | 30kV/3000pF | 10kV | 630mm2 | 2.0km | 30~300Hz | ≤22kV | ||
300mm2 | 3.0km | ||||||||||
120mm2 | 4.5km | ||||||||||
25mm2 | 7.0km | ||||||||||
176/22 | 7.5kVA/1kV/0.4kV | 7.5kW/220/380V | Single node: 44kVA/22kV/55H A total of four | 30kV/3000pF | 10kV | 630mm2 | 2.5km | 30~300Hz | ≤22kV | ||
400mm2 | 3.5km | ||||||||||
300mm2 | 4.0km | ||||||||||
120mm2 | 5.5km | ||||||||||
25mm2 | 9.0km | ||||||||||
220/22 | 10kVA/1kV/ 0.4kV | 11kW/220/380V | Single node: 44kVA/22kV/55H A total of five | 30kV/3000pF | 10kV | 630mm2 | 3.5km | 30~300Hz | ≤22kV | ||
300mm2 | 5.0km | ||||||||||
300mm2 | 5.0km | ||||||||||
120mm2 | 7.0km | ||||||||||
25mm2 | 11.5km | ||||||||||
264/22 | 12kVA/1kV/ 0.4kV | 11kW/220/380V | Single node: 44kVA/22kV/55H A total of six | 30kV/3000pF | 10kV | 630mm2 | 4.0km | 30~300Hz | ≤22kV | ||
300mm2 | 6.0km | ||||||||||
120mm2 | 7.5km | ||||||||||
108/54 | 6kVA/1.5kV/3kV/0.4kV | 5.5kW/220/380V | Single node: 27kVA/27kV/120H A total of four | 60kV/2500pF | 35kV | 300mm2 | 0.5km | 30~300Hz | ≤52kV | ||
120mm2 | 0.6km | ||||||||||
25mm2 | 1.0km | ||||||||||
10kV | 300mm2 | 2.0km | 30~300Hz | ≤22kV | |||||||
120mm2 | 1.5km | ||||||||||
25mm2 | 3.0km | ||||||||||
10kV Electrical Equipment | 30~300Hz | ≤42kV | |||||||||
135/54 | 7.5kVA/1.5kV/3kV/0.4kV | 5.5kW/220/380V | Single node: 33.75kVA/27kV/100H A total of four | 60kV/2500pF | 35kV | 300mm2 | 1.0km | 30~300Hz | ≤52kV | ||
120mm2 | 1.2km | ||||||||||
10kV | 630mm2 | 2.0km | 30~300Hz | ≤22kV | |||||||
300mm2 | 3.0km | ||||||||||
10kV Electrical Equipment | 30~300Hz | ≤42kV | |||||||||
270/54 | 15kVA/1.5kV/3kV/0.4kV | 15kW/220/380V | Single node: 67.5kVA/27kV/50H A total of four | 60kV/2500pF | 35kV | 630mm2 | 1.5km | 30~300Hz | ≤52kV | ||
300mm2 | 2.0km | ||||||||||
120mm2 | 2.5km | ||||||||||
25mm2 | 4.0km | ||||||||||
10kV | 630mm2 | 3.5km | 30~300Hz | ≤22kV | |||||||
300mm2 | 5.0km | ||||||||||
120mm2 | 7.0km | ||||||||||
25mm2 | 10.0km | ||||||||||
75/75 | 4.5kVA/1kV/3kV/0.4kV | 4.5kW/380V | Single node: 37.5kVA/25kV/66H A total of two | 50kV/1000pF | 10kV | 400mm2 | 1.5km | 30~300Hz | ≤22kV | ||
300mm2 | 2.0km | ||||||||||
120mm2 | 2.5km | ||||||||||
25mm2 | 3.0km | ||||||||||
10kV Electrical Equipment | 30~300Hz | ≤42kV | |||||||||
108/108 | 6kVA/1.5kV/3kV/6kV/0.4kV | 5.5kW/220/380V | Single node: 27kVA/27kV/110H A total of four | 100kV/1000pF | 35kV | 630mm2 | 0.4km | 30~300Hz | ≤52kV | ||
300mm2 | 0.6km | ||||||||||
120mm2 | 1.0km | ||||||||||
25mm2 | 1.5km | ||||||||||
10kV | 630mm2 | 1.5km | 30~300Hz | ≤22kV | |||||||
300mm2 | 2.0km | ||||||||||
120mm2 | 2.5km | ||||||||||
25mm2 | 4.0km | ||||||||||
10kV Electrical Equipment | 30~300Hz | ≤42kV | |||||||||
35kV Electrical Equipment | 30~300Hz | ≤95kV | |||||||||
135/108 | 7.5kVA/1.5kV/3kV/6kV/0.4kV | 7.5kW/220/380V | Single node: 33.75kVA/27kV/100H A total of four | 100kV/1000pF | 35kV | 630mm2 | 0.6km | 30~300Hz | ≤52kV | ||
300mm2 | 1.0km | ||||||||||
120mm2 | 1.2km | ||||||||||
25mm2 | 2.0km | ||||||||||
10kV | 630mm2 | 1.8km | 30~300Hz | ≤22kV | |||||||
300mm2 | 2.5km | ||||||||||
120mm2 | 3.5km | ||||||||||
25mm2 | 5.5km | ||||||||||
35kV Electrical Equipment | 30~300Hz | ≤95kV | |||||||||
162/108 | 10kVA/1.5kV/3kV/6kV/0.4kV | 11kW/220/380V | Single node: 40.5kVA/27kV/80H A total of four | 100kV/1000pF | 35kV | 630mm2 | 0.8km | 30~300Hz | ≤52kV | ||
300mm2 | 1.5km | ||||||||||
120mm2 | 2.0km | ||||||||||
25mm2 | 2.5km | ||||||||||
10kV | 630mm2 | 2.0km | 30~300Hz | ≤22kV | |||||||
300mm2 | 3.0km | ||||||||||
120mm2 | 3.5km | ||||||||||
25mm2 | 6.0km | ||||||||||
35kV Electrical Equipment | 30~300Hz | ≤95kV | |||||||||
216/108 | 11kVA/1.5kV/3kV/6kV/0.4kV | 11kW/220/380V | Single node: 54kVA/27kV/68H A total of four | 100kV/1000pF | 35kV | 630mm2 | 1.0km | 30~300Hz | ≤52kV | ||
300mm2 | 1.6km | ||||||||||
120mm2 | 2.5km | ||||||||||
25mm2 | 3.0km | ||||||||||
10kV | 630mm2 | 3.0km | 30~300Hz | ≤22kV | |||||||
300mm2 | 4.0km | ||||||||||
120mm2 | 5.0km | ||||||||||
25mm2 | 8.0km | ||||||||||
35kV Electrical Equipment | 30~300Hz | ≤95kV | |||||||||
270/108 | 15kVA/1.5kV/3kV/6kV/0.4kV | 15kW/220/380V | Single node: 67.5kVA/27kV/50H A total of four | 110kV/1500pF | 35kV | 630mm2 | 1.5km | 30~300Hz | ≤52kV | ||
300mm2 | 2.0km | ||||||||||
120mm2 | 2.5km | ||||||||||
25mm2 | 4.0km | ||||||||||
10kV | 630mm2 | 3.5km | 30~300Hz | ≤22kV | |||||||
300mm2 | 5.0km | ||||||||||
120mm2 | 7.0km | ||||||||||
25mm2 | 10.0km | ||||||||||
35kV Electrical Equipment | 30~300Hz | ≤95kV | |||||||||
160/160 | 10kVA/2.5kV/5kV/10kV/0.4kV | 11kW/220/380V | Single node: 40kVA/40kV/110H A total of four | 160kV/750pF | 35kV | 630mm2 | 0.5km | 30~300Hz | ≤52kV | ||
300mm2 | 0.8km | ||||||||||
120mm2 | 1.0km | ||||||||||
25mm2 | 1.5km | ||||||||||
10kV | 630mm2 | 1.5km | 30~300Hz | ≤22kV | |||||||
300mm2 | 2.0km | ||||||||||
120mm2 | 2.5km | ||||||||||
25mm2 | 4.5km | ||||||||||
35kV Electrical Equipment | 30~300Hz | ≤95kV | |||||||||
110kV Main Transformer, cap≤0.02uF | 45~65Hz | ≤160kV | |||||||||
200/200 | 12kVA/3kV/6kV/12kV/0.4kV | 11kW/220/380V | Single node: 50kVA/50kV/100H A total of four | 200kV/750pF | 35kV | 630mm2 | 0.4km | 30~300Hz | ≤52kV | ||
300mm2 | 0.6km | ||||||||||
120mm2 | 1.0km | ||||||||||
25mm2 | 1.5km | ||||||||||
10kV | 630mm2 | 1.5km | 30~300Hz | ≤22kV | |||||||
300mm2 | 2.0km | ||||||||||
120mm2 | 2.5km | ||||||||||
25mm2 | 4.5km | ||||||||||
35kV Electrical Equipment | 30~300Hz | ≤95kV | |||||||||
110kV Main Transformer, cap≤0.02uF | 45~65Hz | ≤160kV | |||||||||
110kV GIS | 30~300Hz | ≤184kV | |||||||||
500/200 | 25kVA/0.4kV/1.5kV/3kV/6kV/9kV | 25kW/220/380V | Single node: 65kVA/32.5kV/60H A total of eight | 200kV/750pF | 110kV | 300mm2 | 0.8km | 30~300Hz | ≤128kV | ||
35kV | 630mm2 | 1.8km | 30~300Hz | ≤52kV | |||||||
300mm2 | 3.0km | ||||||||||
120mm2 | 3.5km | ||||||||||
25mm2 | 5.0km | ||||||||||
10kV | 630mm2 | 3.0km | 30~300Hz | ≤22kV | |||||||
300mm2 | 6.0km | ||||||||||
120mm2 | 6.0km | ||||||||||
25mm2 | 8.0km | ||||||||||
110kV Main Transformer, cap≤0.02μF | 30~300Hz | ≤160kV | |||||||||
1000/200 | 60kVA/25kV/15kV/7.5kV/3kV/0.2kV/0.4kV | 60kW/220/380V | Single node: 90kVA/45kV/82H Twelve altogether | 550kV/500pF | 110kV | 630mm2 | 1.0km | 30~300Hz | ≤128kV | ||
35kV | 630mm2 | 1.0km | 30~300Hz | ≤52kV | |||||||
300mm2 | 2.0km | ||||||||||
120mm2 | 3.5km | ||||||||||
25mm2 | 5.0km | ||||||||||
10kV | 630mm2 | 2.0km | 30~300Hz | ≤22kV | |||||||
300mm2 | 6.0km | ||||||||||
120mm2 | 6.0km | ||||||||||
25mm2 | 8.0km | ||||||||||
110kV Main Transformer, cap≤0.02μF | 45~65Hz | ≤160kV | |||||||||
216/216 | 12kVA/3kV/6kV/12kV/0.4kV | 11kW/220/380V | Single node: 36kVA/36kV/110H A total of six | 220kV/750pF | 35kV | 630mm2 | 0.6km | 30~300Hz | ≤52kV | ||
300mm2 | 1.0km | ||||||||||
120mm2 | 1.5km | ||||||||||
25mm2 | 2.2km | ||||||||||
10kV(Three of them are grounded) | 630mm2 | 2.0km | 30~300Hz | ≤22kV | |||||||
300mm2 | 3.0km | ||||||||||
120mm2 | 4.0km | ||||||||||
25mm2 | 6.5km | ||||||||||
35kV Electrical Equipment | 30~300Hz | ≤95kV | |||||||||
110kV Main Transformer, cap≤0.02uF | 45~65Hz | ≤160kV | |||||||||
110kVGIS | 30~300Hz | ≤184kV | |||||||||
270/270 | 15kVA/4kV/8kV/16kV/0.4kV | 15kW/220/380V | Single node: 45kVA/45kV/110H A total of nine | 270kV/500pF | 110kV | 300mm2 | 0.2km | 30~300Hz | ≤128kV | ||
35kV | 630mm2 | 0.8km | 30~300Hz | ≤52kV | |||||||
300mm2 | 1.0km | ||||||||||
120mm2 | 1.5km | ||||||||||
25mm2 | 2.0km | ||||||||||
10kV(Three of them are grounded) | 630mm2 | 2.0km | 30~300Hz | ≤22kV | |||||||
300mm2 | 3.0km | ||||||||||
120mm2 | 4.5km | ||||||||||
25mm2 | 7.0km | ||||||||||
110kV Electrical Equipment | 30~300Hz | ≤265kV | |||||||||
110kV Main Transformer, cap≤0.02μF | 45~65Hz | ≤160kV | |||||||||
324/270 | 15kVA/3/5/15kV/0.2kV/0.4kV | 15kW/220/380V | Single node: 54kVA/45kV /100H A total of six | 300kV/500pF | 110kV | 300mm2 | 0.2km | 30~300Hz | ≤128kV | ||
35kV | 300mm2 | 1.0km | 30~300Hz | ≤52kV | |||||||
120mm2 | 1.5km | ||||||||||
25mm2 | 2.0km | ||||||||||
10kV | 630mm2 | 0.8km | 30~300Hz | ≤22kV | |||||||
300mm2 | 3.0km | ||||||||||
120mm2 | 5.0km | ||||||||||
25mm2 | 6.0km | ||||||||||
110kV Electrical Equipment | 30~300Hz | ≤265kV | |||||||||
648/270 | 25kVA/1.5kV/3kV/5kV/15kV/0.2kV/0.4kV | 25kW/220/380V | Single node: 72kVA/45kV /97H A total of nine | 270kV/500pF | 110kV | 300mm2 | 1.0km | 30~300Hz | ≤128kV | ||
35kV | 630mm2 | 0.5km | 30~300Hz | ≤52kV | |||||||
300mm2 | 2.0km | ||||||||||
120mm2 | 3.0km | ||||||||||
25mm2 | 3.5km | ||||||||||
10kV | 630mm2 | 2.0km | 30~300Hz | ≤22kV | |||||||
300mm2 | 5.0km | ||||||||||
120mm2 | 6.0km | ||||||||||
25mm2 | 10.0km | ||||||||||
110kV Electrical Equipment | 30~300Hz | ≤265kV | |||||||||
110kV Main Transformer, cap≤0.02μF | 45~65Hz | ≤160kV | |||||||||
2000/400 | 100kVA/7.5kV/15kV/25k/0.2kV/0.4kV | 100kW/220/380V | Single node: 520kVA/130kV/100H A total of four | 520kV/500pF | 220kV | 630mm2 | 0.1km | 30~300Hz | ≤128kV | ||
110kV | 500mm2 | 0.2km | 30~300Hz | ≤128kV | |||||||
35kV | 630mm2 | 1.8km | 30~300Hz | ≤52kV | |||||||
300mm2 | 3.0km | ||||||||||
120mm2 | 3.5km | ||||||||||
25mm2 | 5.0km | ||||||||||
10kV | 630mm2 | 3.0km | 30~300Hz | ≤22kV | |||||||
300mm2 | 6.0km | ||||||||||
120mm2 | 6.0km | ||||||||||
25mm2 | 8.0km | ||||||||||
220kV Electrical Equipment | 30~300Hz | ≤265kV | |||||||||
648/500 | 30kVA/7.5kV/12.5kV/25kV/0.2kV/0.4kV | 30kW/220V/380V | Single node: 54kVA/45kV Twelve altogether | 500kV/300pF | 220kV | 500mm2 | 0.5km | 30~300Hz | ≤128kV | ||
110kV | 400mm2 | 0.2km | 30~300Hz | ≤128kV | |||||||
35kV | 630mm2 | 1.5km | 30~300Hz | ≤52kV | |||||||
300mm2 | 2.0km | ||||||||||
120mm2 | 3.0km | ||||||||||
25mm2 | 5.0km | ||||||||||
10kV | 630mm2 | 3.0km | 30~300Hz | ≤22kV | |||||||
300mm2 | 6.0km | ||||||||||
120mm2 | 6.0km | ||||||||||
25mm2 | 8.0km | ||||||||||
110kV Electrical Equipment | 30~300Hz | ≤264kV | |||||||||
220kV Electrical Equipment | 30~300Hz | ≤495kV | |||||||||
1080/540 | 60kVA/25kV/15kV/7.5kV/3kV/0.2kV/0.4kV | 60kW/220V/380V | Single node: 90kVA/45kV Twelve altogether | 550kV/500pF | 110kV | 630mm2 | 1.0km | 30~300Hz | ≤128kV | ||
35kV | 300mm2 | 2.0km | 30~300Hz | ≤52kV | |||||||
120mm2 | 3.0km | ||||||||||
25mm2 | 5.0km | ||||||||||
10kV | 400mm2 | 3.0km | 30~300Hz | ≤22kV | |||||||
300mm2 | 6.0km | ||||||||||
120mm2 | 6.0km | ||||||||||
25mm2 | 8.0km | ||||||||||
110kV Electrical Equipment | 30~300Hz | ≤264kV | |||||||||
220kV Electrical Equipment | 30~300Hz | ≤495kV |
Hangzhou High Voltage Technology Co., Ltd. Is a technological enterprise that independently develops, produces and sells high-voltage test equipment! Mainly produce high voltage switches, circuits, transformer direct resistance, on-load tapping, transformer loss parameters, winding deformation, transformers, arresters, generators, partial discharges, dielectric loss tests, frequency resonance withstand voltage tests, earth grid grounding parameters and shunts Vector, secondary and relay protection testing and other high-voltage electrical test equipment.
Obtained 16 international patents and more than 20 software copyright certifications. Self-built 4000 square meters electrical test building, established high-voltage test center and power engineering service team, long-term service for various voltage level test projects and special test projects, relying on the high-voltage test center, at the same time, a high-voltage test undertaking practical operation training class is opened for electric power Industry practitioners provide professional theoretical guidance and practical teaching.
common problem
1. About us
Hangzhou High Voltage Technology Co., Ltd.is a scientific and technological company integrating R&D, production and sales. It independently develops and produces a series of high-voltage test equipment. It was established in 2002 and has a huge production system and business team!
2. Goods inventory and order transportation issues!
After the order is formally formed, the goods will be dispatched within 10 days under normal circumstances. If the purchase volume is large or the customized products are determined according to the actual situation, the goods will be tracked and fed back to the users from time to time during the cargo transportation!
3. Is quality assurance guaranteed?
Twenty years of R&D and production experience, all products have been inspected by the national measurement station, and the quality is guaranteed
4. After-sales service
We promise that all products will provide free two-year warranty, lifetime maintenance, free service information, and online technical services through email, video, etc.
5. Cooperative countries
The products have been successfully exported to the United States, Europe, India, Japan, Australia, Russia and other countries, and distributors have been established in various countries to provide thoughtful services.
contact us:
Hangzhou High Voltage Technology Co., Ltd.
Address: No. 2-15#, Yongtai Road, Renhe Street, Yuhang District, Hangzhou
Contact: Mr. Wang
Send your message to this supplier
People who liked this also liked